DEHNshield
Result: 15/15 Products
Product 941300 was added to Notepad.
Product 941300 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 37.5 kA |
Specific energy [L1+L2+L3-PEN] (W/R) | 352.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 12.5 kA |
Specific energy [L-PEN] (W/R) | 39.06 kJ/ohms |
Nominal discharge current (8/20 µs) [L-PEN]/[L1+L2+L3-PEN] (In ) | 12.5 / 37.5 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, PEN) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, PEN) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Product 941305 was added to Notepad.
Product 941305 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 37.5 kA |
Specific energy [L1+L2+L3-PEN] (W/R) | 352.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 12.5 kA |
Specific energy [L-PEN] (W/R) | 39.06 kJ/ohms |
Nominal discharge current (8/20 µs) [L-PEN]/[L1+L2+L3-PEN] (In ) | 12.5 / 37.5 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, PEN) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, PEN) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm² solid / flexible |
Product 941306 was added to Notepad.
Product 941306 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 22.5 kA |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 7.5 kA |
Nominal discharge current (8/20 µs) [L-PEN]/[L1+L2+L3-PEN] (In ) | 12.5 / 37.5 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, PEN) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, PEN) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm² solid / flexible |
Product 941400 was added to Notepad.
Product 941400 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 12.5 kA |
Specific energy [L,N-PE] (W/R) | 39.06 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L1+L2+L3+N-PE] (In ) | 12.5 / 50 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Product 941405 was added to Notepad.
Product 941405 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 12.5 kA |
Specific energy [L,N-PE] (W/R) | 39.06 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L1+L2+L3+N-PE] (In ) | 12.5 / 50 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Product 941406 was added to Notepad.
Product 941406 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 7.5 kA |
Nominal discharge current (8/20 µs) [L/N-PE]/[L1+L2+L3+N-PE] (In ) | 12.5 / 50 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Product 941310 was added to Notepad.
Product 941310 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 12.5 / 50 kA |
Specific energy [L-N]/[N-PE] (W/R) | 39.06 / 625.00 kJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 12.5 / 50 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 25 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Extended technical data: | --------------------------------- |
Voltage protection level [L-PE] (UP ) | 2.0 kV |
Product 941315 was added to Notepad.
Product 941315 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 12.5 / 50 kA |
Specific energy [L-N]/[N-PE] (W/R) | 39.06 / 625.00 kJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 12.5 / 50 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 25 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | --------------------------------- |
Voltage protection level [L-PE] (UP ) | 2.0 kV |
Product 941316 was added to Notepad.
Product 941316 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 7.5 / 30 kA |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 12.5 / 50 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 25 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | --------------------------------- |
Voltage protection level [L-PE] (UP ) | 2.0 kV |
Product 941200 was added to Notepad.
Product 941200 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 25 kA |
Specific energy [L+N-PE] (W/R) | 156.25 kJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 12.5 kA |
Specific energy [L,N-PE] (W/R) | 39.06 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L+N-PE] (In ) | 12.5 / 25 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 /≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 2 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Product 941205 was added to Notepad.
Product 941205 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 25 kA |
Specific energy [L+N-PE] (W/R) | 156.25 kJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 12.5 kA |
Specific energy [L,N-PE] (W/R) | 39.06 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L+N-PE] (In ) | 12.5 / 25 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 /≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 2 module(s), DIN 43880 |
Approvals | KEMA, VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Product 941206 was added to Notepad.
Product 941206 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 15 kA |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 7.5 kA |
Nominal discharge current (8/20 µs) [L/N-PE]/[L+N-PE] (In ) | 12.5 / 25 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 /≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 25 kArms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 2 module(s), DIN 43880 |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Product 941110 was added to Notepad.
Product 941110 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 25 kA |
Specific energy [L+N-PE] (W/R) | 156.25 kJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 12.5 / 25 kA |
Specific energy [L-N]/[N-PE] (W/R) | 39.06 / 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 12.5 / 25 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 25 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 2 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Extended technical data: | --------------------------------- |
Voltage protection level [L-PE] (UP ) | 2.0 kV |
Product 941115 was added to Notepad.
Product 941115 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 25 kA |
Specific energy [L+N-PE] (W/R) | 156.25 kJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 12.5 / 25 kA |
Specific energy [L-N]/[N-PE] (W/R) | 39.06 / 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 12.5 / 25 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 25 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 2 module(s), DIN 43880 |
Approvals | KEMA, VDE |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | --------------------------------- |
Voltage protection level [L-PE] (UP ) | 2.0 kV |
Product 941116 was added to Notepad.
Product 941116 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 15 kA |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 7.5 / 15 kA |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 12.5 / 25 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 25 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 1.5 mm2 solid / flexible |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 2 module(s), DIN 43880 |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | --------------------------------- |
Voltage protection level [L-PE] (UP ) | 2.0 kV |