DEHNshield ZP (2nd generation)
Result: 1/1 Products
Product 900396 was added to Notepad.
Product 900396 was added to the cart.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 7.5 kA |
Specific energy [L-N] (W/R) | 14.06 kJ/ohms |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 30 kA |
Specific energy [N-PE] (W/R) | 225 kJ/Ohm |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 20 / 80 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Follow current extinguishing capability [L-N] (a.c.) (Ifi ) | 25 kArms |
Follow current extinguishing capability [N-PE] (a.c.) (Ifi ) | 100 Arms |
Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
Max. mains-side overcurrent protection | 160 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range (TU ) | -40 °C ... +80 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (PEN, 9) | 10-35 mm2 fine-stranded / 50 mm2 stranded |
For mounting on | 40 mm busbar systems |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 30 (in combination with cover) |
Capacity | 3 module(s), DIN 43880 |
Approvals | VDE |